Sequencer Config Validator - broken_config and extra_config tests necessarily fail
In the class com.google.daq.mqtt.validator.validations.ConfigValidator, the tests broken_config and extra_config necessarily fail :
In the test setup (com.google.daq.mqtt.validator.SequenceValidator#setUp), the field min_loglevel of the device config is set to 400.
According to the documentation, this means that the device will not report log messages with a level greater than 400 (Level.WARNING).
The tests broken_config and extra_config necessarily fail, because they expect to receive log messages with a level of 200 (Level.INFO). This is less than 400, so the device will not send log messages with a level of 200 and the tests necessarily fail.
I think this is also included in your issue #386
I've taken a look, and it does look like there's something wrong. In my testing, the config loglevel later gets set to 300, but then expects a log entry with a loglevel of 200.
@grafnu I think the loglevel needs to be set to 100, and also Pubber checked as I can pass the test with pubber, so it looks like it's not respecting the min_loglevel?
2022-07-12T14:28:36Z DEBUG sequencer Updated config:
{
"timestamp" : "2022-07-12T14:28:26Z",
"version" : "1.3.13-90-g62cf3663-dirty",
"system" : {
"min_loglevel" : 300,
"metrics_rate_sec" : 600
}
}
2022-07-12T14:28:36Z TRACE sequencer received local_config_2022-07-12T14:28:36Z:
{
"timestamp" : "2022-07-12T14:28:26Z",
"version" : "1.3.13-90-g62cf3663-dirty",
"system" : {
"min_loglevel" : 300,
"metrics_rate_sec" : 600
}
}
2022-07-12T14:28:36Z INFO sequencer finished waiting for device config reset
2022-07-12T14:28:36Z DEBUG sequencer system config extra field null
2022-07-12T14:28:36Z TRACE sequencer received local_system_2022-07-12T14:28:36Z:
{
"min_loglevel" : 300,
"metrics_rate_sec" : 600,
"nonce" : 1657636116412
}
2022-07-12T14:28:36Z DEBUG sequencer update config_system
2022-07-12T14:28:38Z INFO sequencer start waiting for waiting for log message system.config.receive level INFO
I have no doubts that there's lots of things wrong with it. Just because "it worked for me" (when I was coding it up) doesn't mean "it's right" or works in the general sense :-).
The "log level needs to be set to 100" is a bit of a broad statement, so my answer is "maybe." There's a default setting (used by all tests), and then test-specific settings, etc... I would argue that the default setting should likely be 200 or 300 since many debug-level messages will be platform-specific, and so generally not useful for the sequence testing. In specific cases (like with config) it might make sense to have it set to 100 for that one test b/c there is a specific stipulation on a debug message.
On Tue, Jul 12, 2022 at 7:37 AM Noureddine @.***> wrote:
I've taken a look, and it does look like there's something wrong. In my testing, the config loglevel later gets set to 300, but then expects a log entry with a loglevel of 200.
@grafnu https://github.com/grafnu I think the loglevel needs to be set to 100, and also Pubber checked as I can pass the test with pubber, so it looks like it's not respecting the min_loglevel?
2022-07-12T14:28:36Z DEBUG sequencer Updated config: { "timestamp" : "2022-07-12T14:28:26Z", "version" : "1.3.13-90-g62cf3663-dirty", "system" : { "min_loglevel" : 300, "metrics_rate_sec" : 600 } } 2022-07-12T14:28:36Z TRACE sequencer received local_config_2022-07-12T14:28:36Z: { "timestamp" : "2022-07-12T14:28:26Z", "version" : "1.3.13-90-g62cf3663-dirty", "system" : { "min_loglevel" : 300, "metrics_rate_sec" : 600 } } 2022-07-12T14:28:36Z INFO sequencer finished waiting for device config reset 2022-07-12T14:28:36Z DEBUG sequencer system config extra field null 2022-07-12T14:28:36Z TRACE sequencer received local_system_2022-07-12T14:28:36Z: { "min_loglevel" : 300, "metrics_rate_sec" : 600, "nonce" : 1657636116412 } 2022-07-12T14:28:36Z DEBUG sequencer update config_system 2022-07-12T14:28:38Z INFO sequencer start waiting for waiting for log message system.config.receive level INFO
— Reply to this email directly, view it on GitHub https://github.com/faucetsdn/udmi/issues/385#issuecomment-1181841526, or unsubscribe https://github.com/notifications/unsubscribe-auth/AAIEPD322BTHDYRD3SIPYL3VTV7JLANCNFSM525LVUUA . You are receiving this because you were mentioned.Message ID: @.***>